Current-rule reference

EPA 608 Recovery & Evacuation Levels

Choose an appliance and recovery-equipment date for a quick answer, then check the complete table and exceptions below. The displayed values come from EPA's current service-practice summary and 40 CFR 82.156.

Quick finder

Find the listed level

Listed requirement Recover 90%

A small appliance with a functioning compressor and post-1993 recovery equipment requires 90 percent recovery. Evacuation to 4 inches Hg vacuum is an alternative.

The Complete Evacuation Table

Values below are inches of mercury vacuum relative to standard atmospheric pressure of 29.9 inches Hg, except the low-pressure row, which is stated as millimeters of mercury absolute. This table excludes small appliances, MVACs, and MVAC-like appliances.

AppliancePre-Nov. 15, 1993 equipmentOn/after Nov. 15, 1993 equipment
Very-high-pressure appliance0 in. Hg vacuum0 in. Hg vacuum
High-pressure, full charge under 200 lb0 in. Hg vacuum0 in. Hg vacuum
High-pressure, full charge 200 lb or more4 in. Hg vacuum10 in. Hg vacuum
Medium-pressure, full charge under 200 lb4 in. Hg vacuum10 in. Hg vacuum
Medium-pressure, full charge 200 lb or more4 in. Hg vacuum15 in. Hg vacuum
Low-pressure appliance25 mm Hg absolute25 mm Hg absolute

Small-Appliance Recovery Rules

80%Recover 80 percent when
  • Recovery equipment was made before November 15, 1993; or
  • The compressor is not functioning.
90%Recover 90 percent when
  • Recovery equipment was made on or after November 15, 1993; and
  • The compressor is functioning.

Alternative: A person may instead evacuate the small appliance to four inches of mercury vacuum.

Three Traps to Avoid

Equipment date, not appliance date

The table columns refer to when the recovery or recycling equipment was manufactured or imported.

200 pounds belongs to full charge

The split is based on the appliance's full charge, not the amount recovered that day.

Do not mix units

Low-pressure equipment uses 25 mm Hg absolute. Most other table values use inches Hg vacuum relative to atmosphere.

Important Exceptions

Leaking equipment

If leakage makes the table level unattainable or would substantially contaminate recovered refrigerant, isolate leaking from non-leaking components where possible. Evacuate non-leaking components to the listed level and leaking components to the lowest attainable level, no higher than 0 psig.

Non-major repairs

When the equipment will not be evacuated to the environment after a non-major repair, high- or very-high-pressure equipment must reach 0 psig before opening. Low-pressure equipment must be pressurized to 0 psig using an allowed method.

Practice the Table in Context

Independent educational reference; not affiliated with or endorsed by the EPA. It is not a substitute for current regulations, equipment instructions, employer procedures, or professional judgment.